PRODUCT DETAILS
Volume Booster Model PE 500

Salient Features


* High Accuracy 
* Quick Response
* Greater Stability
* Low Air Consumption 
* Large Flow 
* Maintains correct actuator position at high stroking speeds
* Trouble free Service
* Economically priced

Description


The PHIL AIR Booster Relay used when the piping between instrumentation and operational area is long or when operational area has large capacity. Also it can help accelerate actuation speed considerably.
Operation
Signal Pressure enters the input chamber and upper diaphram exerts a downward force on lower diaphram. When the force of the input chamber exceeds the force of lower diaphram, inlet valve permits airflow out the supply port. On signal pressure exhaust the supply valve closes and exhaust flow is opened to permit vent of the secondary air supply to atmosphere. Input output ports are connected by a relief valve which provides exact equalization between the signal and output supply. This will permits a low volume signal to provide high volume output with pressure ratio remaining (1:1) for signal to output.

Specification


Supply Pressure                               : Max 140 psig 
Signal Pressure                                : Max 100 psig 
Output Pressure                               : Max 100 psig 
Flow Capacity                                  : 10 scfm 
Linearity                                           : Within +- 1% 
Hysteresis                                        : Within 1% 
Cv factor                                          : 1.1 
Pressure ratio                                   : 1:1 
Ambient & Fluid Temperature           : -5 to 70° C 
Port Size                                           : 1/4" 
Weight                                              : 620gms